Waterstops in construction joints in the bill of quantities
| Unit | lin. m |
|---|---|
| Category | Joints and waterstops |
| Division | Waterproofing and thermal insulation |
The item as worded in the bill
Supply and install polyvinyl chloride waterstops 25 cm wide in construction joints between the raft and the basement and tank walls and in vertical construction joints, of the centre-bulb type at expansion joints, held at mid-section by tying to the reinforcement; the rate includes heat-welding of splices, factory-made intersection pieces and split stop-end formwork.
Method of measurement
Measured by the linear metre on the joint centre line, each width and type separately, weld overlap and wastage not added. The horizontal raft-to-wall joint is taken on the wall centre line around the perimeter, and vertical joints are added at wall height at each pour break shown on the drawings. Intersection pieces fall within the length unless the bill enumerates them. Swelling strips are measured under another item.
What the unit rate covers
- Supply of waterstop of the specified width and type
- Fixing at mid-section by tying to the reinforcement
- Heat-welding of splices on site
- Factory-made pieces for corners and intersections
- Split stop-end formwork
- Protection from damage and sun until the next pour
Priced separately
- Water-swelling strips
- Roughening and cleaning the construction joint surface
- External waterproofing of the walls
- Injection of leaking joints after testing
Specification and reference
The project technical specification sets the waterstop material, width and profile for each type of joint, and the construction joint requirements of Saudi Building Code SBC 304 apply. The manufacturer’s instructions on heat-welding and bending radius are followed. A shop drawing showing the waterstop route and intersections must be submitted before delivery.
What moves the rate
- Waterstop width and profile type
- Number of intersections, corners and factory-made pieces
- Number of vertical pour breaks
- Wall thickness and steel congestion at the joint
Common pricing mistakes
- Taking off the horizontal joint between raft and walls and forgetting vertical joints at every pour break in long walls.
- Pricing the flat type for all joints although expansion joints require the dearer centre-bulb type.
- Leaving out factory-made intersection pieces and assuming hand-welded site fabrication that the engineer rejects.
- Forgetting the joints of the lift pit, pump rooms and fire water tank, which are water-retaining structures like the main tank.
Related calculators and terms
More items in Joints and waterstops
Price your whole bill of quantities
Upload the bill of quantities and its items are priced from published references, each with its price source.
Start nowجرّب بلا تسجيل