Home › BOQ items guide › Waterproofing and thermal insulation › Foundation waterproofing › Bituminous coating to foundations

Bituminous coating to foundations in the bill of quantities

Unitm²
CategoryFoundation waterproofing
DivisionWaterproofing and thermal insulation

The item as worded in the bill

Supply and apply to all concrete and block surfaces in contact with soil, including footings, column necks, ground beams and walls below ground level, a primer and two coats of cold-applied bituminous paint at the coverage in the manufacturer’s data sheet, after cleaning surfaces, repairing defects and plugging formwork tie holes; the rate includes protecting the coating until backfilling.

Method of measurement

Measured in square metres of the surface actually coated, not the plan area: footing top and four sides, neck perimeter over its buried height, both sides of the ground beam and its top if buried, and both faces of block walls below ground. The footing underside and the part of its top under the neck are not measured. The area is measured once whatever the number of coats.

What the unit rate covers

Priced separately

Specification and reference

The project technical specification and the approved manufacturer’s data sheet govern, setting the number of coats, coverage and drying time. The soil report’s recommendations and the damp-protection requirements for foundations in SBC 201 and 303 are consulted, with SBC 304 for the durability of concrete exposed to sulphates and chlorides. Asphalt primer conforms to ASTM D41.

What moves the rate

Common pricing mistakes

Related calculators and terms

More items in Foundation waterproofing

Price your whole bill of quantities