Internal lining of water tanks in the bill of quantities
| Unit | m² |
|---|---|
| Category | Wet areas and tanks waterproofing |
| Division | Waterproofing and thermal insulation |
The item as worded in the bill
Supply and apply internal lining to the underground concrete water tank in a crystalline cementitious coating approved for drinking water contact, in two coats to the floor, walls, roof soffit and internal columns, after plugging tie holes, repairing honeycombing and forming fillets; the rate includes pipe penetration treatment, a fill test, and cleaning and disinfecting the tank before handover.
Method of measurement
Measured in square metres of the internal surfaces actually coated: the floor at internal dimensions; walls on their internal perimeter over the height the item states, full or to water level; the roof soffit where required; and the perimeter of columns and both faces of dividing walls. The access opening and pipes are not deducted, nor is the area multiplied by coats. Dimensions come from the tank’s structural drawings.
What the unit rate covers
- Cleaning the concrete and removing release agents
- Plugging formwork tie holes and repairing honeycombing
- Fillets between floor and walls
- Two lining coats at the stated coverage
- Treatment around pipes
- Fill test, cleaning and disinfection
Priced separately
- External waterproofing of the tank
- Waterstops embedded in the tank’s construction joints
- Injection of structural cracks
- Ladder, cover and pipework
Specification and reference
The lining material must carry a certificate from an accredited body of suitability for drinking water contact, and is applied to the project specification and manufacturer’s data sheet. Drinking water tank requirements of Saudi Building Code SBC 701 and those of SBC 304 for low-permeability concrete exposed to water apply. A fill test for the specified period precedes acceptance.
What moves the rate
- Lining type: crystalline or flexible cementitious, or epoxy
- Condition of the concrete surface and extent of repair
- Tank depth and difficulty of ventilation and lighting inside
- Whether the roof soffit and columns are included
Common pricing mistakes
- Measuring floor and walls and forgetting the roof soffit, internal columns and dividing walls between tank compartments.
- Pricing an ordinary waterproofing material without a drinking-water suitability certificate, which is rejected at submittal.
- Ignoring the cost of the fill-test water, its disposal and its holding period, especially in large tanks.
- Not allowing for confined-space requirements: forced ventilation, safe lighting and an attendant at the opening.
Related calculators and terms
More items in Wet areas and tanks waterproofing
Price your whole bill of quantities
Upload the bill of quantities and its items are priced from published references, each with its price source.
Start nowجرّب بلا تسجيل