Switches and socket outlets in the bill of quantities
| Unit | No. |
|---|---|
| Category | Lighting and wiring accessories |
| Division | Electrical works |
The item as worded in the bill
Supply and install a twin 13 A switched socket outlet with three rectangular pin holes, 250 V, with a white thermoplastic or metal faceplate to the approved sample, mounted on a recessed metal box; the rate includes fixing screws, connection of the phase, neutral and earth wires, and polarity and earth continuity testing.
Method of measurement
Measured by number for each type: one-, two- or three-gang switch, two-way (staircase) switch, single or twin socket, weatherproof socket, power outlet for air conditioner or heater with isolating switch. A multi-gang switch on one box is counted as one piece. Where the item is an ‘inclusive point’, the switch or socket is carried in it and not counted again. Floor sockets are counted under a separate item.
What the unit rate covers
- Switch or socket with faceplate
- The recessed box where not part of the conduit work
- Connection and earth wire termination
- Levelling and fixing
- Polarity and operation testing
Priced separately
- Conduits and wires up to the box
- Data, telephone and television outlets
- The circuit breaker in the board
Specification and reference
Governed by SBC 401 and by the Saudi standard for household plugs and socket outlets; the type adopted in the Kingdom has three rectangular pins rated 13 A at a nominal voltage of 230 V. Every socket must be earthed and shuttered, with a suitable protection degree in wet and outdoor locations and safe distances from baths and basins.
What moves the rate
- Quality grade and faceplate material
- Number of gangs or outlets per piece
- Standard, weatherproof or floor-mounted
- Quantity and a single range throughout the project
Common pricing mistakes
- Counting switches from the number of lighting points, although one switch may control several points and a staircase needs two.
- Pricing an ordinary socket for the air conditioner or heater outlet when a higher-rated double-pole isolating switch with indicator is described.
- Choosing a range before sample approval, then the owner asks for a dearer range in a colour to suit the decor after contract signature.
- Omitting weatherproof sockets on the roof, in the garden and outdoor kitchen, which are shown on the site plan.