Copper wiring in the bill of quantities
| Unit | lin. m (or within the point rate) |
|---|---|
| Category | Conduits and wiring |
| Division | Electrical works |
The item as worded in the bill
Supply and draw in single-core PVC-insulated copper wires, rated 450/750 V, 2.5 mm² cross-section, in the installed conduits for socket circuits, in three colours for phase, neutral and earth; the rate includes connection tails inside boards and boxes, termination in connectors, circuit labelling, and insulation resistance and continuity testing, to the load schedule and specification.
Method of measurement
Measured in linear metres for each cross-section separately, every wire counted individually, so a single-phase circuit of three wires is measured at three times its route length. Length follows the conduit route with rises and drops. Connection tails inside boards and boxes and wastage are not measured but carried in the rate per metre. Where pricing is per point, wires are included in the point and not measured.
What the unit rate covers
- Wires of the specified size and voltage rating
- Drawing into conduits
- Connection tails and connectors
- Colour coding and circuit labelling
- Insulation and continuity testing
Priced separately
- Conduits and boxes
- Circuit breakers in the distribution boards
- Switches, sockets and light fittings
Specification and reference
Executed to SBC 401, which sets the minimum size for lighting and socket circuits, the permitted voltage drop and conductor colours. Copper wires are supplied to IEC 60227 or the corresponding Saudi standard, with insulation rated at 70 °C or higher as specified; a separate earth wire is required in every circuit, and joints inside conduits are not allowed.
What moves the rate
- Wire size and the copper price on the day of purchase
- Circuit lengths and distance of the board from the loads
- Insulation type: standard or low-smoke halogen-free
- Source of the wires and their approval
Common pricing mistakes
- Counting two wires per circuit and forgetting the earth wire, so a third of the quantity is missing in single-phase lighting and socket circuits.
- Pricing air conditioner and heater circuits at the socket circuit size, when the load schedule calls for larger sizes and dedicated circuits.
- Fixing the copper price from an old quotation, when the gap between tender and wire pulling may exceed a year.
- Ignoring a metre or more of tails at every board; in a building with many boards they total whole coils.
A published price for its main material