العربية Try the demo Start now
Home › BOQ items guide › Electrical works › Conduits and wiring › Copper wiring

Copper wiring in the bill of quantities

Unitlin. m (or within the point rate)
CategoryConduits and wiring
DivisionElectrical works

The item as worded in the bill

Supply and draw in single-core PVC-insulated copper wires, rated 450/750 V, 2.5 mm² cross-section, in the installed conduits for socket circuits, in three colours for phase, neutral and earth; the rate includes connection tails inside boards and boxes, termination in connectors, circuit labelling, and insulation resistance and continuity testing, to the load schedule and specification.

Method of measurement

Measured in linear metres for each cross-section separately, every wire counted individually, so a single-phase circuit of three wires is measured at three times its route length. Length follows the conduit route with rises and drops. Connection tails inside boards and boxes and wastage are not measured but carried in the rate per metre. Where pricing is per point, wires are included in the point and not measured.

What the unit rate covers

Priced separately

Specification and reference

Executed to SBC 401, which sets the minimum size for lighting and socket circuits, the permitted voltage drop and conductor colours. Copper wires are supplied to IEC 60227 or the corresponding Saudi standard, with insulation rated at 70 °C or higher as specified; a separate earth wire is required in every circuit, and joints inside conduits are not allowed.

What moves the rate

Common pricing mistakes

A published price for its main material

The monthly Kingdom-wide average as published by the General Authority for Statistics, with its monthly series: 2.5mm national electrical wires

Related calculators and terms

More items in Conduits and wiring

Price your whole bill of quantities

Upload the bill of quantities and its items are priced from published references, each with its price source.

Start nowجرّب بلا تسجيل