Main distribution board in the bill of quantities
| Unit | No. |
|---|---|
| Category | Distribution boards |
| Division | Electrical works |
The item as worded in the bill
Supply and install a low-voltage main distribution board, floor-standing in powder-coated sheet steel, protection degree IP54, with copper busbars and an air or moulded-case main circuit breaker of the rating and breaking capacity shown on the single-line diagram, moulded-case outgoing breakers, digital meters and indicator lamps; the rate includes the base frame, termination, earthing, factory and site tests and commissioning.
Method of measurement
Measured by number, each board under its name with the components shown on the single-line diagram; breakers, busbars and meters are not measured separately. The automatic transfer switch panel and the power factor correction panel are measured under their own items even when lined up with the main board, unless the description merges them. Any breaker added after shop drawing approval is treated as a variation.
What the unit rate covers
- Enclosure, doors and copper busbars
- Main breaker and outgoing breakers
- Meters, current transformers and indicator lamps
- Base frame and fixing
- Shop drawings and factory tests
- Termination, earthing and commissioning
Priced separately
- Incoming and outgoing cables
- Concrete plinth and cable trench
- Automatic transfer switch panel and power factor correction capacitors
Specification and reference
The board is built and tested to IEC 61439 by an approved panel builder and installed to SBC 401 and Saudi Electricity Company requirements. Breaking capacity follows the calculated short-circuit current at the board, the form of separation and protection degree follow the project specification, voltage is 230/400 V at 60 Hz, and service clearances are kept around the board.
What moves the rate
- Main breaker rating and breaking capacity
- Number and sizes of outgoing breakers
- Form of internal separation and protection degree
- Origin of breakers and level of metering
Common pricing mistakes
- Pricing the board from the main breaker rating alone and ignoring the breaking capacity, which raises the class of every breaker.
- Relying on a panel builder’s quotation made without the specification, pricing a lower form of separation and smaller busbars than the engineer will demand.
- Forgetting that the board will not pass through the electrical room door once blockwork is complete, requiring a temporary opening or site assembly.
- Missing the breakers for pumps, lifts and the fire pump, which appear on the mechanical drawings, not on the first single-line diagram.