Low-voltage power cables in the bill of quantities
| Unit | lin. m |
|---|---|
| Category | Cables and containment |
| Division | Electrical works |
The item as worded in the bill
Supply and lay a low-voltage copper cable, 0.6/1 kV, four-core 4×25 mm², cross-linked polyethylene insulated and PVC sheathed (XLPE/PVC), on cable trays or in conduits; the rate includes copper lugs and glands at both ends, fixing with cable ties or cleats, identification tags, insulation resistance testing and connection to both boards.
Method of measurement
Measured in linear metres for each size, number of cores and type (armoured or unarmoured) separately, along the actual route from the termination in the first board to that in the second. No allowance is added for wastage or drum remnants. Parallel cables of one feeder are each measured at full length. The accompanying earth conductor is measured under its own item unless it is a core of the cable.
What the unit rate covers
- Cable of the specified size and number of cores
- Pulling and laying on trays or in conduits
- Lugs and glands at both ends
- Cleats or ties and identification tags
- Insulation testing and connection to the boards
Priced separately
- Cable trays and conduits
- Excavation, backfill and protection tiles for buried cables
- Fire-stopping of penetrations
Specification and reference
Sizes are selected under SBC 401 from load current, installation method, ambient temperature, cable grouping and voltage drop; summer heat in Saudi Arabia makes the correction factors significant. Cables are supplied to IEC 60502 with stranded copper conductors and factory test certificates, armour is required for directly buried cables, and the minimum bending radius is respected.
What moves the rate
- Size, number of cores and copper weight
- Armoured or unarmoured
- Copper or aluminium
- Route length and difficulty of pulling in shafts
Common pricing mistakes
- Measuring the route on plan only and missing the rise in vertical shafts, which may equal the building height for every feeder.
- Pricing an unarmoured cable when the description requires steel-wire armour for the buried section between the building and the electrical room.
- Neglecting lugs and glands for large sizes; each end needs a hydraulic crimping tool and skilled labour.
- Ordering cables to drawing lengths before measuring the route on site, so a drum falls short of a feeder and jointing is not accepted.
A published price for its main material
The monthly Kingdom-wide average as published by the General Authority for Statistics, with its monthly series: 25mm national Electrical cables
Related calculators and terms
More items in Cables and containment
Price your whole bill of quantities
Upload the bill of quantities and its items are priced from published references, each with its price source.
Start nowجرّب بلا تسجيل