Electrical conduits in the bill of quantities
| Unit | lin. m (or within the point rate) |
|---|---|
| Category | Conduits and wiring |
| Division | Electrical works |
The item as worded in the bill
Supply and install heavy-gauge rigid PVC electrical conduits, 20 mm diameter, embedded in concrete slabs and walls; the rate includes bends, couplers and solvent-welded joints, pull, junction and outlet boxes, tying to the reinforcement before casting, chasing blockwork and making good, end caps and draw wire, all to the drawings and specification.
Method of measurement
Measured in linear metres along the centre line for each diameter and type, without deducting bends and boxes; embedded runs are kept apart from exposed, and metal from plastic. Vertical drops to switches, sockets and boards are added by mounting height. In many bills conduits have no item of their own and are carried in the lighting and power points, so they are taken off for costing, not payment.
What the unit rate covers
- Conduits of the specified diameter and class
- Bends, couplers and adaptors
- Pull, junction and outlet boxes
- Fixing, chasing and making good
- Draw wire and end caps
Priced separately
- Wires and cables inside the conduits
- Cable trays and metal trunking
- Underground ducts for external cables
Specification and reference
Executed to SBC 401 and the project specification, which limit the number of wires in each diameter and the bends between two pull boxes. Conduits are supplied to IEC 61386 in the heavy, non-flame-propagating class; metal conduits are galvanised, earthed and electrically continuous throughout, and the minimum concrete cover over conduits embedded in slabs is maintained.
What moves the rate
- Diameter and class: light or heavy gauge
- PVC or galvanised steel
- Embedded in concrete or exposed on supports
- Density of boxes and bends
Common pricing mistakes
- Taking conduits off the plan without the drops to switches and sockets, which add a substantial length in every room.
- Leaving out empty conduits for low-current systems and air conditioning, shown on drawings other than the lighting and power layouts.
- Pricing the light class for conduits in slabs; they are crushed under workers’ feet and the concrete pump hose and become blocked.
- Not allowing for labour standing by during casting to guard the conduits and repair any that separate before the concrete sets.