Home › BOQ items guide › Electrical works › Conduits and wiring › Electrical conduits

Electrical conduits in the bill of quantities

Unitlin. m (or within the point rate)
CategoryConduits and wiring
DivisionElectrical works

The item as worded in the bill

Supply and install heavy-gauge rigid PVC electrical conduits, 20 mm diameter, embedded in concrete slabs and walls; the rate includes bends, couplers and solvent-welded joints, pull, junction and outlet boxes, tying to the reinforcement before casting, chasing blockwork and making good, end caps and draw wire, all to the drawings and specification.

Method of measurement

Measured in linear metres along the centre line for each diameter and type, without deducting bends and boxes; embedded runs are kept apart from exposed, and metal from plastic. Vertical drops to switches, sockets and boards are added by mounting height. In many bills conduits have no item of their own and are carried in the lighting and power points, so they are taken off for costing, not payment.

What the unit rate covers

Priced separately

Specification and reference

Executed to SBC 401 and the project specification, which limit the number of wires in each diameter and the bends between two pull boxes. Conduits are supplied to IEC 61386 in the heavy, non-flame-propagating class; metal conduits are galvanised, earthed and electrically continuous throughout, and the minimum concrete cover over conduits embedded in slabs is maintained.

What moves the rate

Common pricing mistakes

Related calculators and terms

More items in Conduits and wiring

Price your whole bill of quantities

Upload the bill of quantities and its items are priced from published references, each with its price source.

Start nowجرّب بلا تسجيل