Distribution boards in the bill of quantities
Boards distribute power and protect circuits. The main board receives the supply from the company meter or transformer and generator and feeds the sub-boards; it is floor-standing with moulded-case or air circuit breakers and copper busbars. Sub-boards are wall-mounted with miniature circuit breakers feeding lighting, socket and air-conditioning circuits on each floor or flat. Automatic transfer switch panels, power factor correction panels and motor control panels are added as required. Boards are assembled locally by approved panel builders with components named in the description or subject to approval.
Where it sits in the bill and what comes before it on site
Listed by number, each board under its name on the single-line diagram. Before installation, the electrical room or wall recess must be plastered and painted, shop drawings approved, and the feeder cables and earthing system available.
Items in this category
| Item | Unit |
|---|---|
| Main distribution board | No. |
| Sub-distribution boards | No. |
What is often left out when pricing it
- Board shop drawings and their approval, and factory tests witnessed by the engineer where the specification requires.
- The concrete plinth or steel frame under floor-standing boards, and the trench or cable entry openings.
- Spare breakers and spare ways required in every board for future extension.
- The insulating rubber mat in front of the boards, nameplates, and the single-line diagram fixed inside the door.
Frequently asked questions
How do I price a board when the bill gives only its name?
Go to the single-line diagram and load schedule for that board and extract the main breaker rating and breaking capacity, the outgoing breakers with their ratings and poles, and the metering and earth-leakage protection. Send these with the specification to an approved panel builder for a detailed quotation, then add transport, installation, termination and testing.
Which Saudi Electricity Company requirements affect pricing?
The company sets requirements for the meter room or box and its position on the property boundary, for the main breaker type and rating by contracted load, and for earthing. Large loads need a transformer room of stated dimensions, ventilation and access. Non-compliance delays energisation, so obtain its current requirements before pricing.
Are residual current devices included in the board price?
Yes, where they appear on the single-line diagram or board schedule they are part of its components. The electrical code requires earth-leakage protection for socket circuits, bathrooms and outdoor circuits. They increase the number of modules and the board width, so check the panel builder’s quotation includes them with the required sensitivity and type.