Gypsum board partitions in the bill of quantities
| Unit | m² |
|---|---|
| Category | Drywall partitions |
| Division | Plaster, paint and gypsum works |
The item as worded in the bill
Supply and install internal gypsum board partitions of overall thickness as shown on the drawings, of galvanised steel studs and tracks at 600 mm centres, lined on each face with one 12.5 mm gypsum board, with mineral wool cavity infill, joints taped and filled and door openings strengthened; the rate includes flexible sealant at the perimeter and preparation for painting.
Method of measurement
Measured in square metres of partition area on one face, being the centre-line length by the height actually built from floor to slab or to above the suspended ceiling. Door and internal window openings are deducted; small service openings are not. Each partition type is measured separately by number and type of boards and stud size, and strengthening of openings and corners is not measured separately.
What the unit rate covers
- Floor and head tracks, studs and their fixings
- Boards to both faces and screws
- Mineral wool infill where required
- Tape, compound and corner beads
- Strengthening of door jambs and heads
- Flexible sealant at the perimeter
Priced separately
- Doors and their frames
- Paint or final cladding
- Special backing for heavy fixtures where a separate item exists
- Fire stopping around service penetrations
Specification and reference
Boards comply with ASTM C1396 and framing with ASTM C645, installed and finished to the manufacturer’s instructions. The work falls under the Saudi general building code SBC 201; where a fire rating is required the partition is built as a complete tested assembly under the fire code SBC 801 and Civil Defense requirements, with no component substituted.
What moves the rate
- Partition height and the stud size it requires
- Number and type of boards per face
- Fire-resistance or sound-insulation requirement
- Number of openings, corners and junctions
Common pricing mistakes
- Measuring the partition only up to the suspended ceiling when the sections show it running to the concrete slab for fire or acoustic reasons.
- Pricing a narrow stud for a tall partition, when the greater height imposes a wider stud or heavier gauge under the manufacturer’s tables.
- Merging fire-rated or double-layer partitions with the standard partition in one rate without separating the area of each type.
- Leaving out mineral wool and acoustic sealant at the perimeter of partitions between hotel rooms and closed offices where sound insulation is specified.