Water booster pumps in the bill of quantities
| Unit | No. (set) |
|---|---|
| Category | Tanks and pumps |
| Division | Plumbing and drainage |
The item as worded in the bill
Supply and install a water booster set of two multi-stage centrifugal pumps (one duty, one standby) of the flow and head shown in the equipment schedule, on a common base frame, with a diaphragm pressure vessel and a control panel with variable speed drive and dry-run protection; the rate includes valves, non-return valves, vibration isolators, commissioning and testing.
Method of measurement
Measured by number for the complete set or the single pump as described, stating flow, head and number of pumps. The set covers everything between the suction and discharge flanges: pumps, headers, valves, pressure vessel and control panel. Pipework outside the flanges is measured under the pipe items, and the feeder cable to the panel under electrical works. Submersible pumps and transfer pumps to the roof tank have separate items.
What the unit rate covers
- Pumps and motors on a common base frame
- Suction and discharge headers, valves and non-return valves
- Diaphragm pressure vessel, pressure switches and transmitters
- Control panel and dry-run protection
- Vibration isolators and flexible connectors
- Commissioning and pressure setting
Priced separately
- Concrete plinth under the set
- Power feeder cable up to the panel
- Pipework beyond the set limits
Specification and reference
The system is governed by SBC 701 for minimum and maximum pressure at the fixtures, and by SBC 401 for motors, panels and earthing. The duty point comes from the equipment schedule, wetted parts suit potable water, the contractor submits the pump performance curve and factory test certificate, and noise and vibration limits are observed in pump rooms near dwellings.
What moves the rate
- Flow, head and number of pumps
- Fixed speed or a variable speed drive per pump
- Pump material: stainless steel or cast iron
- Control panel level and its link to the building management system
Common pricing mistakes
- Comparing offers by motor horsepower instead of duty point, so a pump is supplied that cannot reach the pressure at the top floor.
- Pricing a single pump where the bill calls for duty and standby with automatic changeover, or forgetting the pressure vessel and its switch.
- Omitting the pressure-reducing valve for lower floors in tall buildings, needed when pressure exceeds the fixture limit.
- Not checking the motor voltage and frequency against the supply available on site before issuing the purchase order.