Wall-mounted split unit in the bill of quantities
| Unit | No. |
|---|---|
| Category | Split air conditioning |
| Division | HVAC and fire fighting |
The item as worded in the bill
Supply and install wall-mounted split air conditioner, cooling capacity 18,000 Btu/h, inverter compressor, rated for hot climate T3, with a valid Saudi energy-efficiency label; the rate includes indoor and outdoor units, outdoor unit bracket, insulated copper piping and control cable up to 5 m length, evacuation, charging, start-up and testing.
Method of measurement
Measured by number for each complete unit (indoor and outdoor), classified by cooling capacity and compressor type. Piping covered by the item is not measured again; any length beyond the stated limit is measured in linear metres along the actual route between the two units, vertical runs included. No allowance is made for wastage or spare units unless the bill says so.
What the unit rate covers
- Indoor unit, outdoor unit and remote controller
- Outdoor unit bracket or base with vibration pads
- Insulated copper and control cable up to the length stated in the item
- Coring the wall and making good the opening
- Evacuation, refrigerant charging, start-up and testing
- Manufacturer’s warranty certificate
Priced separately
- Power supply point and isolator
- Copper lengths beyond the included length
- Buried first-fix piping where carried out under a separate item
- Drain pipe to the drain point where it has its own item
Specification and reference
Governed by the Saudi mechanical code SBC 501 and the energy conservation code SBC 602 for residential buildings or SBC 601 for others, and by the Saudi standards authority’s energy-efficiency requirements and mandatory label. Installation follows the manufacturer’s instructions on maximum piping length, level difference between the units and the airflow and maintenance clearances around the outdoor unit.
What moves the rate
- Cooling capacity and compressor type (fixed speed or inverter)
- Energy-efficiency rating and warranty period
- Copper run length and outdoor unit position (wall or roof)
- Number of units in one order
Common pricing mistakes
- Basing the unit rate on a short run while the drawings put the outdoor units on the roof, several times beyond the included length.
- Leaving out the additional refrigerant charge the manufacturer requires once the piping exceeds the pre-charged length.
- Pricing fixed-speed units when the specification calls for an inverter compressor at a stated efficiency rating.
- Forgetting facade brackets for outdoor units and the scaffolding or boom lift needed to fix them on upper floors.