Refrigerant copper piping in the bill of quantities
| Unit | lin. m (per pair or per diameter) |
|---|---|
| Category | Refrigerant piping and condensate drain |
| Division | HVAC and fire fighting |
The item as worded in the bill
Supply and run a pair of seamless copper refrigerant pipes (1/4 in. liquid line and 1/2 in. gas line) with wall thickness suited to the working pressure, each line separately insulated with 13 mm closed-cell elastomeric rubber; the rate includes control cable, brazing under nitrogen purge, clips, pressure test and capping of the ends.
Method of measurement
Measured in linear metres along the actual route from the outdoor unit valve to the indoor unit connection, including risers, drops and bends, not the horizontal distance on plan. The item states whether measurement is per pair or per single line by diameter. Nothing is added for wastage or for connection tails at the ends, and insulation and clips are carried in the unit rate.
What the unit rate covers
- Copper pipes in the specified diameters and wall thicknesses
- Rubber insulation to each line and wrapping tape
- Accompanying control cable
- Bends, brazed joints, brazing alloy and nitrogen
- Clips, supports and sleeves at penetrations
- Nitrogen pressure test and capping of the ends
Priced separately
- Additional refrigerant charge
- Metal or plastic protective trunking for exposed runs
- Chasing and making good in existing walls
- Branch joints for variable refrigerant flow systems
Specification and reference
Governed by the Saudi mechanical code SBC 501. Pipes are copper made for refrigeration and air-conditioning service to ASTM B280, clean and capped, with a wall thickness that withstands the pressure of the refrigerant used. Brazing is done under nitrogen purge, the network is tested with dry nitrogen then evacuated before charging, and exposed insulation is protected from sunlight.
What moves the rate
- Pipe diameter and wall thickness
- Insulation thickness and its protection on exposed runs
- Route length and number of bends and risers
- Buried runs versus exposed runs on supports
Common pricing mistakes
- Measuring the horizontal distance on plan and ignoring the rise to the roof and the drop to the unit, losing several metres per unit.
- Pricing thin-walled commercial copper that cannot take the pressure of current refrigerants, so it is rejected at material approval.
- Insulating both lines in one sleeve or the gas line only, although inverter units require each line insulated separately.
- Leaving rubber insulation exposed on the roof without tape or trunking, so it perishes in the sun and is replaced at the contractor’s cost.