Variable refrigerant flow system in the bill of quantities
| Unit | No. (units) or lump sum (system) |
|---|---|
| Category | Central air conditioning |
| Division | HVAC and fire fighting |
The item as worded in the bill
Supply and install variable refrigerant flow air-conditioning system comprising outdoor units with inverter compressors of the capacities shown in the schedules and indoor units of the specified types and capacities; the rate includes branch joints, thermostats, central controller, communication cabling, additional refrigerant charge, and start-up and testing by the authorised agent.
Method of measurement
Outdoor units are measured by number according to capacity, and indoor units by number classified by type (wall, cassette, ducted) and capacity. Copper pipes are measured in linear metres per diameter and branch joints by number, or the network is merged into a lump sum item. Where the whole system is a lump sum, the contractor prepares his own detailed take-off from the drawings and equipment schedules.
What the unit rate covers
- Outdoor and indoor units with their accessories
- Branch joints and headers
- Thermostats and central controller
- Communication cabling between units
- Additional refrigerant charge according to network lengths
- Start-up, programming and testing by the agent
Priced separately
- Copper network and its insulation where separately billed
- Ducts and outlets for ducted indoor units
- Condensate drainage
- Power supply to outdoor and indoor units
Specification and reference
Governed by the Saudi mechanical code SBC 501, including its limits on refrigerant quantity in occupied spaces, and the equipment efficiency requirements of SBC 601. Installation follows the manufacturer’s manual on maximum pipe length, level differences and the ratio of indoor to outdoor capacity, and shop drawings reviewed by the agent before work starts.
What moves the rate
- Total capacity and the number and types of indoor units
- Copper network lengths and building height
- System type (cooling only, or cooling and heating)
- Level of central control and link to the building management system
Common pricing mistakes
- Pricing the system per ton of refrigeration without breaking down indoor unit types, although cassette, ducted and wall units differ clearly in price.
- Leaving out branch joints and the additional refrigerant charge, both of which are calculated from the network drawing, not the unit count.
- Forgetting brazing under nitrogen purge and the extended pressure test, both conditions set by the agent for start-up and warranty.
- Leaving communication cabling and the power feed to each indoor unit unpriced, with responsibility unclear between the HVAC and electrical contractors.
Related calculators and terms
More items in Central air conditioning
Price your whole bill of quantities
Upload the bill of quantities and its items are priced from published references, each with its price source.