Condensate drain piping in the bill of quantities
| Unit | lin. m (or point) |
|---|---|
| Category | Refrigerant piping and condensate drain |
| Division | HVAC and fire fighting |
The item as worded in the bill
Supply and install uPVC condensate drain pipes, 32 mm diameter, with solvent-welded fittings, laid to a continuous fall of not less than 1 percent towards the drain, insulated with 9 mm elastomeric rubber inside suspended ceilings; the rate includes clips, supports, a trap at the unit and a water flow test.
Method of measurement
Measured in linear metres per diameter along the pipe centre line from the unit drain pan outlet to the discharge point; bends, tees and traps are carried in the unit rate. Where the item is written per point, one point is counted for each indoor unit whatever the length. Small condensate pumps are measured by number, and insulation is measured separately only where it has its own item.
What the unit rate covers
- Pipes, fittings and solvent cement
- Clips and supports that hold the fall
- Rubber insulation on runs liable to sweat
- Trap and cleaning access where needed
- Water flow and leak test
Priced separately
- Condensate pumps
- Floor drains and drainage stacks
- Chasing and making good in existing buildings
- Secondary emergency pan line where required
Specification and reference
Governed by the Saudi mechanical code SBC 501 for condensate disposal, falls and minimum diameters, and by the plumbing code SBC 701 for indirect connection to the drainage system. Pipes and fittings are of a material approved in the specification, and units whose drain pan works under negative pressure are given a trap to the manufacturer’s depth.
What moves the rate
- Diameter and route length to the drain
- Need for insulation or a condensate pump
- Runs buried in walls versus suspended runs
- Number of units collected on one line
Common pricing mistakes
- Pricing a point on an assumed short length, then finding from the drawings that the nearest drain is at the flat’s far end.
- Omitting insulation on the drain pipe inside the suspended ceiling, so it sweats and stains the ceiling tiles after first operation.
- Not checking that the ceiling void allows the fall along the whole route, forcing the contractor into unpriced condensate pumps.
- Collecting many units on a line of the same diameter without enlarging it, so the engineer orders the main line replaced after installation.
Related calculators and terms
More items in Refrigerant piping and condensate drain
Price your whole bill of quantities
Upload the bill of quantities and its items are priced from published references, each with its price source.