Galvanised steel ductwork in the bill of quantities
| Unit | m² (or kg) |
|---|---|
| Category | Central air conditioning |
| Division | HVAC and fire fighting |
The item as worded in the bill
Supply, fabricate and install rectangular air ducts of galvanised steel sheet, thickness graded with duct size from 0.6 to 1.2 mm, fabricated to low-pressure duct construction standards; the rate includes joints, flanges, seam sealant, hangers and supports, fittings such as bends, branches and reducers, and access doors, and excludes thermal insulation and dampers.
Method of measurement
Measured in square metres of sheet surface: the perimeter of the section multiplied by the length along the duct centre line, with bends, branches and reducers taken at their actual area. No area is added for seam laps, flanges or cutting waste; these are carried in the unit rate. Quantities are classified by sheet thickness, and flexible ducts are measured in linear metres per diameter.
What the unit rate covers
- Galvanised sheet in the specified thicknesses
- Flanges, angles, stiffeners and sealant
- Hangers, threaded rods and fixings
- Bends, branches, reducers and turning vanes
- Access doors and flexible connections at equipment
- Cutting and fabrication waste
Priced separately
- Thermal and acoustic insulation
- Volume control dampers and fire dampers
- Air outlets and their plenum boxes
- Leakage testing and air balancing where separately billed
Specification and reference
Governed by the Saudi mechanical code SBC 501, and by the energy conservation code SBC 601 for duct insulation and sealing. The sheet is hot-dip galvanised to ASTM A653, and thicknesses, stiffening, jointing methods and hanger spacing are set by duct size and pressure class under the SMACNA duct construction standards or as the project specification states.
What moves the rate
- Sheet thickness and the proportion of fittings to straight lengths
- Hanging height and congestion of other services in the ceiling
- Pressure class and required sealing level
- Total quantity and scope for machine fabrication in the workshop
Common pricing mistakes
- Taking off straight lengths only and ignoring the area of bends, branches and reducers, a large share of the area in congested buildings.
- Converting area to weight at one thickness throughout, although thickness rises with size and steel weighs about 7.85 kg per m² per millimetre.
- Ignoring cutting waste from standard sheets, which rises with small duct sizes and a high number of fittings.
- Assuming insulation is within the duct rate, when most bills carry it separately with different thicknesses for internal and exposed ducts.