Grilles and diffusers in the bill of quantities
| Unit | No. (or lin. m for linear diffusers) |
|---|---|
| Category | Central air conditioning |
| Division | HVAC and fire fighting |
The item as worded in the bill
Supply and install square four-way ceiling diffuser of extruded aluminium, face size 600×600 mm, powder coated in the approved colour, with opposed-blade volume damper; the rate includes the insulated plenum box behind the diffuser, an insulated flexible duct connection not exceeding two metres in length, fixing and balancing.
Method of measurement
Diffusers and grilles are measured by number, classified by type and nominal size, checking whether the stated size is the neck or the face size. Linear diffusers are measured in linear metres according to the number of slots, and external louvres by number or in square metres. Each item states whether a damper and plenum box are included, and an included flexible duct is not measured again.
What the unit rate covers
- Diffuser or grille with frame and blades
- Volume damper where the item states it
- Plenum box and flexible connection where the item states them
- Coating in the approved colour
- Fixing in ceiling or wall, and balancing
Priced separately
- Main and branch ductwork
- Openings in the suspended ceiling and their trimming
- Fire dampers
- Door grilles where carried under joinery items
Specification and reference
Governed by the Saudi mechanical code SBC 501 and the project specification. Outlets are selected from the manufacturer’s performance tables by air quantity, throw and permitted noise level, and a sample in the required colour is approved before supply. External fresh air louvres are fitted with sand traps and protective mesh in dust-prone areas.
What moves the rate
- Type, size and material (aluminium or steel)
- Whether a damper and plenum box are included
- Special non-standard coating colour
- Quantity and standardisation of sizes
Common pricing mistakes
- Confusing neck size with face size when asking for prices, so the diffuser supplied does not fit the 600×600 ceiling tile.
- Pricing the diffuser alone and leaving out the plenum box, flexible duct and clamps, which the duct items do not measure.
- Treating a return grille like a supply diffuser, although it usually has no damper and may carry a filter and hinges.
- Counting linear diffusers by number without their actual lengths, end caps and the inactive sections the architect requires.