Refrigerant piping and condensate drain in the bill of quantities
This category groups the first-fix work that precedes fixing the air conditioners: copper pipes carrying refrigerant between indoor and outdoor units, and pipes draining the condensed water from indoor units. Soft copper in coils is used for small diameters and hard copper in straight lengths for larger ones, insulated with closed-cell elastomeric rubber. Drains are run in plastic pipes at a continuous fall to the nearest drain point, with a small condensate pump where a fall cannot be achieved.
Where it sits in the bill and what comes before it on site
These items sit at the start of the mechanical section as first-fix work. They are installed after blockwork and before plastering when buried in walls, or before the suspended ceiling is closed when suspended, and are tested before being covered.
Items in this category
| Item | Unit |
|---|---|
| Refrigerant copper piping | lin. m (per pair or per diameter) |
| Condensate drain piping | lin. m (or point) |
What is often left out when pricing it
- Nitrogen pressure testing of the copper and sealing the ends until the units are fixed.
- Insulating drain pipes inside suspended ceilings to prevent sweating and stained ceiling tiles.
- Protective trunking for exposed copper on roofs and facades, and shielding the insulation from sunlight.
- Sleeves through walls and slabs, and fire-stopping of the openings where required.
Frequently asked questions
Is copper measured per line or per pair?
It varies between bills. Some measure the pair (liquid and gas lines together) per linear metre classified by unit capacity; others measure each diameter separately. Read the item and the preambles closely, because confusing the two methods doubles or halves the quantity.
When is first fix priced per point?
In villas and flats the item is sometimes written per point, covering copper, insulation, control cable and drain for one unit. That works when distances are similar, but the average actual length is taken from the drawings: a point with its outdoor unit on the roof differs greatly from one on the same wall.
Where does the condensate go?
To the nearest floor drain, a dedicated drain stack or to the outside, as the drawings show. The connection to the drainage system is indirect, through an air gap or trap, so that odours do not return. The drain position sets the pipe length, so check it before fixing a rate per point.