Lightning protection in the bill of quantities

Unitlump sum (or lin. m for conductors and No. for terminals)
CategoryEarthing and low-current systems
DivisionElectrical works

The item as worded in the bill

Supply and install a conventional lightning protection system of copper air terminals at the highest roof points, a mesh of 25×3 mm copper tape on the parapet and roof, down conductors on the facades each with a test joint, and dedicated earth electrodes bonded to the building earthing; the rate includes fixings, bonding of metal roof equipment and testing.

Method of measurement

Measured as a lump sum for the complete system to the drawings, or in detail: air terminals by number, roof and down conductors in linear metres on their actual route following the parapet and bends, test joints by number, and earth electrodes by number with their pits. A down conductor runs from roof level to the earth electrode. An early streamer emission head is counted by number with its mast.

What the unit rate covers

Priced separately

Specification and reference

The system is designed to IEC 62305 after a risk assessment that sets the protection level, mesh size and down conductor spacing, with earthing and bonding to SBC 401. Materials are copper or aluminium of the standard’s minimum sections, sharp bends are not allowed, the system is bonded to the building earthing, with surge protection at the main board.

What moves the rate

Common pricing mistakes