Raised access floor in the bill of quantities
| Unit | m² |
|---|---|
| Category | Resilient and wood flooring |
| Division | Flooring and cladding |
The item as worded in the bill
Supply and install a raised access floor of 600×600 mm panels with a cementitious core in a steel shell or of calcium sulphate, with a high-pressure laminate or anti-static vinyl top finish, on adjustable galvanised steel pedestals to 30 cm finished height, with stringers, pedestal bases bonded to the concrete slab, earthing of the system and cutting at perimeters.
Method of measurement
Measured in square metres of net area between walls, with the finished height and load class stated. Openings for air outlets and floor electrical boxes are not deducted; perforated panels, air outlets and boxes are measured by number under separate items. Ramps, steps and edge fascias at floor edges are measured in linear metres or by number. Cutting of perimeter panels and the additional supports beneath them are not measured.
What the unit rate covers
- Panels with the specified top finish
- Pedestals, heads and stringers
- Pedestal base adhesive and levelling
- Cutting perimeter panels and their supports
- Earthing of the system
- Panel lifter and spare panels where stated
Priced separately
- Perforated panels and air outlets
- Electrical floor outlet boxes
- Ramps, steps and edge fascias
- Anti-dust sealer to the concrete slab where a separate item exists
Specification and reference
Raised floors are classified and tested under EN 12825 for concentrated load and deflection, or as specified. The specification fixes load class, height and surface electrical resistance in computer rooms. It falls under the general building code SBC 201 and the fire code SBC 801 for materials and the underfloor void, and is earthed under the electrical code SBC 401.
What moves the rate
- Floor height and load class
- Panel core material and top finish
- Stringers or a stringerless system
- Number of cut-outs, ramps and cut perimeters
Common pricing mistakes
- Pricing a panel of office load class for a server room that requires a higher class, stronger pedestals and stringers.
- Overlooking the ramp, steps and edge fascia at the room entrance, which are required where the raised level ends at the door.
- Ignoring cleaning and anti-dust sealing of the concrete slab before installation, a condition where the void is used for air distribution.
- Treating perimeters as full panels with no extra pedestals, although every panel cut at the wall needs its own support.
Related calculators and terms
More items in Resilient and wood flooring