Fire sprinkler system in the bill of quantities

UnitNo. (heads) and lin. m (pipes)
CategoryFire fighting
DivisionHVAC and fire fighting

The item as worded in the bill

Supply and install automatic pendent quick-response fire sprinkler head, K-factor 5.6, temperature rating 68 °C, complete with escutcheon plate, listed and approved for fire service; the rate includes connection to the branch line and inclusion in the network pressure test; black steel pipes and valves are measured under their own items.

Method of measurement

Sprinkler heads are measured by number, classified by type (pendent, upright, sidewall, concealed) and temperature rating. Pipes are measured in linear metres per diameter along the centre line without deducting fittings; elbows, tees and hangers are carried in the pipe rate. Zone control valves, alarm valves and flow switches are measured by number. Quantities come from approved shop drawings, not preliminary tender drawings.

What the unit rate covers

Priced separately

Specification and reference

Governed by the fire code SBC 801 and the general building code SBC 201 on which buildings require sprinklers; the system is designed and installed to NFPA 13 for hazard classification, head spacing and hydraulic calculations. Pipes are black steel to ASTM A53 or equivalent, the network is hydrostatically tested, and Civil Defense approves drawings and materials before installation.

What moves the rate

Common pricing mistakes

Related calculators and terms

More items in Fire fighting

Price your whole bill of quantities

Upload the bill of quantities and its items are priced from published references, each with its price source.

Start nowجرّب بلا تسجيل