Fire hose cabinets in the bill of quantities
| Unit | No. |
|---|---|
| Category | Fire fighting |
| Division | HVAC and fire fighting |
The item as worded in the bill
Supply and install recessed fire hose cabinet of red-painted sheet steel with glazed door, containing a hose reel with 25 mm semi-rigid rubber hose 30 m long, shut-off nozzle and valve, and a 2.5 in. landing valve for Civil Defense use; the rate includes connection to the riser, instruction sign and testing.
Method of measurement
Measured by number for each complete cabinet, classified by contents (hose reel, lay-flat hose on a rack, landing valve, or combined), method of fixing (recessed or surface) and cabinet material. Risers and feed lines are measured in linear metres under the pipe items, and pressure reducing valves by number where required. The wall recess is not part of this item.
What the unit rate covers
- Cabinet with door, lock and instruction sign
- Hose reel, or lay-flat hose and its rack
- Nozzle and valves inside the cabinet
- Connection to the feed line or riser
- Fixing, pressure and flow testing
Priced separately
- Risers and feed lines
- Wall recess and finishing of its edges
- Extinguisher inside the cabinet where separately billed
- External fire brigade inlet connection
Specification and reference
Governed by the fire code SBC 801 and Civil Defense requirements for cabinet positions and the distances covered by the hose. The standpipe and hose system is designed to NFPA 14, which classifies systems by user: occupants, firefighters or both; valves, hoses and nozzles are listed and approved for fire service.
What moves the rate
- Cabinet contents (reel only, or with landing valve and hose)
- Cabinet material (painted steel or stainless steel)
- Recessed or surface fixing
- Need for pressure reducing valves on lower floors
Common pricing mistakes
- Confusing a hose reel cabinet with a landing valve cabinet holding a lay-flat hose; each has different contents and a different price.
- Leaving out pressure reducing valves on the lower floors of towers, where pressure at the hose outlet exceeds the permitted limit.
- Pricing a recessed cabinet without checking wall thickness; a thin or fire-rated wall may force a surface-mounted cabinet.
- Forgetting the branch feed line from the riser to the cabinet when the cabinet stands several metres from the riser.